Product Description

Product Description

NAJS automatic flash speed multi-position transformer calibration device, is the South Australian Electric Company to adapt to the modern transformer calibration fast and accurate characteristics of the development of a new generation of transformer calibration device. The device consists of NAJS automatic flash speed multi-position transformer calibration device, the current load box, control cabinet, current transformer test stand and other components. In the premise of maintaining the original technical characteristics of the current transformer in the rapid measurement of the rapid positioning of test points, and the load box, a variety of variable ratio of the transformer cover, etc. have been greatly improved.

Product Features

(1) The fine adjustment of the device uses a programmable source technology, the test point of the positioning more quickly and accurately.

(2) the device in a number of current transformer measurement speed has been a qualitative improvement in the 3-5 minutes of time can be measured in any of the twelve transformers than any current transformer.

(3) The device is equipped with 5A standard current transformer, the current load box configuration 5A load value of 2.5VA-60VA, the voltage load box configuration 100V load value from 1.25VA-158.75VA basically meet the requirements of users. The load box can be switched automatically during measurement.

(4) The device can be used for the regulation of the transformer and non-regulation of the measurement, the user can specify the measurement of any percentage of the measurement.

Technical indicators

(1) environmental conditions

Temperature: 5 ° C to 40 ° C

Relative humidity: <80% (25 )

Altitude: <2500m

Power frequency: 50Hz ± 0.5Hz

Power supply voltage: 220V ± 5V

(2) Measuring range:

F: 0.0000% to 200.0% δ: 0.000 'to 999.9'

R: 0.0000? To 60.0? X: 0.0000? To 60.0? G: 0.0000 mS to 60.0 mS

Measurement objects: CT, PT, impedance, admittance.

(3) the basic error:

In-phase component: ΔX = ± (X × 2% + Y × 2% ± 2 words)

Quadrature component: ΔY = ± (Y × 2% + ± X × 2% × 34.38) ± 5 words

"X", "Y" - the displayed value of the instrument

"5 words" - quantization error of the instrument

Dial indicator: Level 1

(4) Scope of work:

Current: (1% -149%) In (In = 5A)

(5% -149%) In (In = 1A)

Workload: Current: To for Tx <0.12? Cos? = 1.0

(5) Dimensions (mm)

Horizontal table body: 1500 (L) × 780 (W) × 1030 (H)

Vertical platform body: 670 (L) × 630 (W) × 1570 (H)

Payment Terms︰T/T
Product Image






Related Products
Standard Voltage Transformer
Standard Voltage Transformer
US $ 900
Lightning Impulse Current Generator
Lightning Impulse Current Generator
US $ 1000
Lightning Impulse Voltage Generator
Lightning Impulse Voltage Generator
US $ 1000
Insulated Boots gloves withstand Voltage Tester
Insulated Boots gloves withstand Voltage Tester
US $ 1000




Home  |  Product Catalog  |  News  |  Contact Us  |  Sitemap  |  Mobile Version
  简体版     繁體版     English

Powered by DIYTrade.com  Build your FREE website !